Eclipse / Embrass Peerless Universal Circulating Pump
- Affected
- Circulating Pumps manufactured by Cacheng Machinery & Electric Company Ltd between 2017 and 2025.
- The problem
- The product presents a serious risk of electric shock. The mains cable can be connected to the pump in reverse, allowing the live pin to connect to the earth pin.
- What to do
- An installed pump can remain in operation, but you must take care not to handle affected pumps as there is a serious risk of electrocution.
Product information
| Type | Electrical appliances and equipment – Circulating pumps for heating systems |
|---|---|
| Brand | Eclipse (Embrass Peerless for use in heating systems) |
| Affected product code | 490920 |
| Manufacturer reference | CFA 25-50-130 |
| Country of Origin | China |
| Product Description | Circulating Pumps manufactured by Cacheng Machinery & Electric Company Ltd between 2017 and 2025. |
| Product Report and Image | Link to product image and PDF |
Hazard
The product presents a serious risk of electric shock. The mains cable can be connected to the pump in reverse, allowing the live pin to connect to the earth pin and causing accessible metal parts to become live.
The product does not meet the requirements of the Electrical Equipment (Safety) Regulations 2016.
Corrective action
An installed pump can remain in operation, but you must take care not to handle affected pumps as there is a serious risk of electrocution.
Embrass Peerless have launched a replacement programme and are advising consumers who own an affected pump to conduct a visual inspection. Do not touch the pump or its housing.
Visually inspect the mains connection to the pump. If the connection is connected so that the clip is at the bottom and connected and the three plastic lines are at the top and connecting to the “three lines” on the pump housing, then your pump is correctly installed.
If the mains connection is connected with the clip to the top, and the three lines on the bottom, your mains electrical connection is not fitted correctly. Immediately take a photograph of the pump in situ and then email to it to technical@embrasspeerless.co.uk. Installed units of the Eclipse Universal Circulating Pump should only be replaced or serviced by an approved, qualified service engineer or installer.
For further information, please access: Safety Notice – Eclipse Circulating Pump – Embrass Peerless or contact Embrass Peerless via telephone on 0121 744 3900.
Additional information
PSD notification number: 2607-0037
Notified by: Office for Product Safety and Standards
Can I get a refund?
In most cases, yes – recalled items can usually be returned for a full refund, repair or replacement, often without a receipt. Follow the instructions in the notice above, or contact the shop you bought it from. More on your rights after a recall.
Updated 7 July 2026. This page summarises an official notice. Details can change – always follow the official notice.